The Boiler Control 268 is designed to stage multiple boilers using Outdoor Temperature Reset. It can be used in applications ranging from baseboard or mixed radiant heating systems, to dedicated domestic hot water heating in commercial buildings. This control regulates a single heating water temperature through Outdoor Temperature Reset and/or Setpoint/DHW target control. It is capable of controlling (stage and rotate) up to 9 on/off boilers as well as the system pump.
- Submittal Sheet
- Data Brochure
Features
-
Advanced settings to fine-tune building requirements
-
Automatic Boiler Differential
-
Boiler Pump operation (optional)
-
Control up to 9 On-Off boilers
-
DHW Priority (optional)
-
DHW pump or valve operation
-
Equal Run Time Rotation
-
Exercising
-
Outdoor Temperature Reset
-
Powered system pump output
-
Quick setup for easy installation and programming of control
-
Setback input for energy savings
-
Test sequence to ensure proper component operation
-
User comfort adjustment to increase or decrease building space temperature
-
Warm Weather Shut Down
Specifications
Control | Microprocessor control. This is not a safety (limit) control |
Packaged weight | 3.3 lb. (1500 g) |
Dimensions | 6-5/8″ H x 7-9/16″ W x 2-13/16″ D (170 x 193 x 72 mm) |
Enclosure | Blue PVC plastic, NEMA type 1 |
Approvals | CSA C US, meets class B: ICES & FCC Part 15 |
Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Non-condensing |
Power supply | 115 V (ac) ±10%, 50/60 Hz, 600 VA |
Relay | 230 V (ac) 5 A, 1/3 hp |
Demands | 20 to 260 V (ac) 2 VA |
Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
-Included | Outdoor Sensor 070, 2 of Universal Sensor 082, and 500 Ω Resistor |
-Optional | tekmar type #: 033, 071, 082 |
Warranty | Limited 3 Year Warranty |