The Universal Reset Module 422 is designed to operate all of the mechanical equipment in a hydronic heating system, except for zones, coordinating their operation through network communication. It can be used in applications ranging from a single zone of baseboard with an on/off boiler to multiple fan coils, mixed radiant floor zones, and a modulating/condensing boiler. This control regulates up to two heating water temperatures through Outdoor Temperature Reset and Indoor Temperature Feedback. It is capable of controlling a single on/off, two stage, or modulating boiler, a mixing device, Domestic Hot Water, setpoint loads, and can expand up to 24 zones in total for each heating water temperature.
- Submittal Sheet
- Data Brochure
- Wiring Brochure
Features
-
Automatic Boiler Differential
-
Boiler Protection
-
DHW Post Purge
-
DHW Priority (optional)
-
DHW control
-
Exercising
-
Expandable up to 48 zones
-
Indoor Temperature Feedback
-
One touch overrides (with optional User Switch)
-
Outdoor Temperature Reset
-
Powered pump outputs
-
Single on/off or modulating boiler control
-
System Setback (with optional Timer)
-
Variable Speed, or Floating action mixing control
-
Warm Weather Shut Down
-
Zone Synchronization
Specifications
Control | Microprocessor PID control; This is not a safety (limit) control |
Packaged weight | 1.87 lb. (848 g) |
Dimensions | 3-5/8″ H x 5-3/8″ W x 9/16″ D (92 x 137 x 14 mm) |
Approvals | CSA C US, CSA/UL 61010-1, meets Class B: ICES & FCC Part 15 |
Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), Max. RH 92% for temperatures up to 40°C, 50% RH at > 40°C, Altitude <6560 feet (2000 m), Installation Category II, Pollution Degree 2 |
Power Supply | Provided by interconnected tekmarNet Zone Manager |
Pump relays | 115 V (ac) 5 A, 1/6 hp |
Boiler Relay | 115 V (ac) 5 A |
Variable pump | 115 V (ac) 2.5 A, fuse T2.5 A 250 V |
Combined Load | 10 A Max. (for DHW, Primary, Mixing & Var. Speed Pump) |
Floating Action Output | 24 V (ac) 8 VA Maximum |
Modulation Output | 0-10 V (dc) Minimum 2500 |
Demands | 20-260 V (ac) / 0.1 VA @ 24 V |
Sensors | NTC thermistor, 10k @ 77°F (25°C ± 0.2°C) ß=3892 |
-Included | Outdoor Sensor 070 and 2 of Universal Sensor 082 |
Warranty | Limited 3 Year Warranty |